LIYY

-5°C / +70°C

Larger Image

General Specifications Structure Technical Specifications Cross Section

Applications

They are used as low frequency cable in electronic control systems,
signal control and information communication technology.
Electrolytic copper is insulated with TI1 PVC thermoplastic polymer. PES tape is wrapped overall cores. TM1 PVC thermoplastic polymer sheath is applied.


Standards

PCT
ROHS
TSEK
CE

Structure

1. Conductor : Electrolytic flexible copper
2. Insulation : TI1 PVC
3. Separator : PES tape
4. Sheath : TM1 PVC

Technical Specifications

1. Conductor : EN 60228 class 5
2. Operating voltage : 300 / 500 V
3. Test voltage : 1500 V
4. Operating temperature : -5 °C...+70 °C
5. Storage temperature max. : +40 ºC
6. Reference standards : TSE ÜBM - 03 - BK - 022
DIN VDE 815
DIN VDE 472
DIN VDE 207
7. Mechanical tests : DIN VDE 207
DIN VDE 472
EN 60811-1-2
EN 60811-1-4
EN 60811-3-1
EN 60811-3-2
8. Electrical tests : IEC 60885-1
9. Flame retardance vertical flame propagation : EN 60332-1-2